- SIGNA™ Hero 3.0T Service Methods
- 5852800-8EN Revision 1.0
- 00000018WIA306CB230GYZ
- id_156672361.9
- Jul 13, 2021 4:27:36 PM
FPU Sensor Replacement
Prerequisites
| Required persons | Preliminary requirements | Procedure | Finalization |
|---|---|---|---|
| 1 | Not Applicable | 60 minutes | 15 minutes |
| Item | Quantity | Effectivity | Part number | Manufacturer |
|---|---|---|---|---|
| Standard Tool | 1 | - | - | - |
| Flashlight | 1 | - | - | - |
| 20L Draining Tank (Shipped with System) | 2 | - | - | - |
| Water Hand Pump (Shipped with System) | 1 | - | - | - |
| Draining Hoses (Shipped with System) | 2 | - | - | - |
| Water Shield Tape | As needed | - | - | - |
| Item | Quantity | Effectivity | Part number | Manufacturer |
|---|---|---|---|---|
| Towels | 2 or 3 | - | - | - |
| Item | Quantity | Effectivity | Part number | Manufacturer |
|---|---|---|---|---|
| FPU | 1 | - |
Refer to FRU Manual | - |
| ||||
Procedure
Finalization
- Turn on the F50 cryocooler.
- Turn on the “Main Power Switch”.
- Turn on the “Drive Switch”.
- Turn on ISC Power. Refer to Removing LOTO - ISC.
- Perform Water Flow Adjustment per following steps.
- Insert SSA Service Key.
- Open Common Service Desktop and select .
- Click Run and check Customer Coolant Flow Rate and check if displayed Customer Coolant Flow Rate is in between 50L/min and 80L/min. Note: Typical Value of water flow is 60L/min (15.8gpm)
Figure 16. Cabinet Monitor Functional Diag 
- If the displayed value is between 50L/min and 80L/min, go to next step (3.e)
If coolant flow rate is out of specification, adjust the FPU bypass valve until the coolant flow satisfies the specification.
-
To increase Facility Water Flow : Turn the Bypass valve to Clockwise. Maximum Water Flow when Bypass valve is at Vertical Position.
-
To reduce Facility Water Flow : Turn the Bypass valve to Counter Clockwise. Minimum Water Flow when Bypass valve is at Horizontal position.
Note: Click Run Button of Functional Diag each time when measuring.Figure 17. FPU Bypass valve 
-
- Check the F-50 Water Flow by Magnet Monitor. (Press Data key, then press Down key to show Water_Flow)
Figure 18. Magnet Monitor operation 
- Adjust the water flow by adjusting the F-50 supply water valve so that water flow becomes within 7~10 L/min. If it’s difficult to adjust the water flow within 7~10 L/min, adjust the water flow by referring to admissible range (water flow vs. water temperature) shown in Figure 20.
Figure 19. F-50 Supply Valve Adjustment 
Figure 20. Cryocooler Water Cooling Requirements 
- Perform check scan.













