• SIGNA™ Hero 3.0T Service Methods
  • 5852800-8EN Revision 1.0
  • Object ID: 00000018WIA30EBB230GYZ
  • Topic ID: id_15667047 Version: 1.8
  • Date: Jul 13, 2021 4:27:37 PM

FPU Replacement

Prerequisites

Table 1. Personnel requirements
Required personsPreliminary requirementsProcedureFinalization
1Not Applicable90 minutes15 minutes
Table 2. Tools and test equipment
ItemQuantityEffectivityPart numberManufacturer
Standard Tool1---
20L Draining Tank2---
Water Hand Pump1---
150MM FUNNEL1---
Table 3. Consumables
ItemQuantityEffectivityPart numberManufacturer
TowelsNA---
Table 4. Replacement parts
ItemQuantityEffectivityPart numberManufacturer
FPU 1-

Refer to FRU Manual

-
Table 5. Safety
Table 6. Required conditions
ConditionReferenceEffectivity

ISC Power must be turned OFF. Refer to Lockout / Tagout for ISC.

--

F50 Power must be OFF. Refer to SRDK Cryocooler Service Manual (5351735).

--

Procedure

  1. Open ICC Cover.
    Note: If Service space is narrow, remove the door.
  2. Confirm that ISC and Cryocooler power are OFF.
  3. Close valves of Facility water.
  4. Disconnect the FPU sensor cable connector from 3X11 of Control Unit.
    Figure 1. Disconnect the FPU sensor cable
  5. Disconnect GCU and CCU Quick Disconnects.
    Figure 2. Quick Disconnects
  6. Drain the ICC primary water circuit to the tank per following steps.
    1. Connect the draining hose to the emergency valve (a) and place the tank to the other side. Then, open valve of (a).
    2. If no more coolant leak from (a), disconnect hose, connect it to emergency valve (b), and open valve of (b).
      Note: Leave the valve (a) opened.
    3. If no more coolant leak from (b), disconnect hose, connect it to fill & drain valve (c), and open valve of (c).
      Note: Leave the valve (a) and (b) opened.
    Figure 3. Draining
  7. Loosen a captive screw and slightly slide the FPU out from ICC to access to the hoses.
    Figure 4. Slide FPU
  8. Disconnect Facility water and F-50 hoses from ICC.
    Figure 5. Disconnect Hoses
  9. Press the release tabs and remove FPU.
    Figure 6. Remove FPU
  10. Remove the sensor cable by removing pin toward your side and install it to the new FRU.
    Figure 7. Remove the sensor cable
  11. Remove rails from FPU and attach them to the new FRU.
  12. Install FPU by reverse order of removal.

Finalization

  1. Open valves of Facility Water and check that there is no water leakage at any hoses connected to FPU.
  2. Turn on the F50 cryocooler and ISC power.
  3. Turn on ISC Power. Refer to Removing LOTO - ISC.
  4. Perform check scan.